Home > Control Techniques Drives > Commander Sk An Authorized distributor of Control Techniques

Commander SK

Specifications

Control

  • Open loop vector control
  • Speed or torque control
  • Speed reference input: 0-10 V, 0-20 mA, 4-20 mA,
    (-10 to +10 V SM-I/O Lite option)
  • 4 digital inputs
    – World (enable, run forward, run reverse, local/remote)
    – USA (not stop, run, jog, local/remote)
  • Switching frequency: 3 (default) – 6 – 12 – 18 kHz
  • Output frequency 0 to 1500 Hz
  • Accel and Decel ramps (linear and S type)
  • Positive logic control
  • Serial communication
    – Modbus RTU RS485 via R J45 connector
    – Baud rate 4800, 9600, 19200 or 38400 bits per second
  • DC injection braking as standard
  • Dynamic braking transistor as standard
  • Dynamic motor flux V/Hz for energy saving
  • Quadratic motor flux V/Hz for fan and pump optimisation

Protection

  • Undervoltage, Supply and DC Link overvoltage, Phase loss,
    Drive overload, Instantaneous overcurrent, Short circuit,
    Ground fault, Drive thermal, Watchdog, Motor thermal

General Characteristics

  • Maximum overload 150% of rated current for 60s
  • Intelligent Thermal Management (ITM) optimises switching frequency
  • 8 preset speeds
  • Flying start
  • Mains dip ride through
  • Automatic no-spin autotune for fast performance optimisation
  • Keypad access to all parameters for more demanding set-ups

Environment

  • IP20
  • NEMA 1 rating with optional cover
  • Ambient temperature -10 to +40°C @ 3 kHz switching
  • Humidity 95% maximum (non-condensing)
  • Electromagnetic Emissions complies with EN61800-3 (second environment) as standard.
  • Complies with EN6000-6-3 (residential) and EN61000-6-4 (industrial) generic standards with optional footprint filter

Approvals & Listings

 

UL, cUL

UL File Listed 8D14

IEC

Meets IEC Vibration, Mechanical Shock
and Electromagnetic Immunity Standards

CE

Low Voltage Directive

NEMA

NEMA 1 enclosure type

ISO 9001:2000

Certified Manufacturing Facility

ISO 14001

Certified Manufacturing Facility

Contact Us

Automation Stock / Rome Electric
36 Westside Industrial Blvd.
Rome, GA 30165
Phone:706-413-1560
Fax: 706-232-2071

Email: sales@automationstock.com

test

See Also:
100 / 120 VAC; ±10% 1 phase
  Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SKB1100075       4 0.75 1
SKB1100110       5.2 1.1 1.5

200 / 240 VAC; ±10% 1 phase
Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SKA1200025       1.7 0.25 0.33
SKA1200037       2.2 0.37 0.5
SKA1200055       3 0.55 0.75
SKA1200075       4 0.75 1
SKBD200110       5.2 1.1 1.5
SKBD200150       7 1.5 2
SKCD200220       9.6 2.2 3

200 / 240 VAC; ±10% 3 phase
  Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SKBD200110       5.2 1.1 1.5
SKBD200150       7 1.5 2
SKCD200220       9.6 2.2 3
SK2202 22 5.5 7.5 17 4 5
SK2203 28 7.5 10 25 5.5 7.5
SK3201 42 11 15 31 7.5 10
SK3202 54 15 20 42 11 15
SK4201 68 18.5 25 56 15 20
SK4202 80 22 30 68 18.5 25
SK4203 104 30 40 80 22 30
SK5201 130 37 50 105 30 40
SK5202 154 45 60 130 37 50

575 VAC; ±10% 3 phase
  Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SK3501 5.4 3 3 4.1 2.2 2
SK3502 6.1 4 5 5.4 3 3
SK3503 8.4 5.5 7.5 6.1 4 5
SK3504 11 7.5 10 9.5 5.5 7.5
SK3505 16 11 15 12 7.5 10
SK3506 22 15 20 18 11 15
SK3507 27 18.5 25 22 15 20
SK4603 36 22 30 27 18.5 25
SK4604 43 30 40 36 22 30
SK4605 52 37 50 43 30 40
SK4606 62 45 60 52 37 50
SK5601 84 55 75 63 45 60
SK5602 99 75 100 85 55 75
SK6601 125 90 125 100 75 100
SK6602 144 110 150 125 90 125

380 / 480 VAC; ±10% 3 phase
  Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SKB3400037       1.3 0.37 0.5
SKB3400055       1.7 0.55 0.75
SKB3400075       2.1 0.75 1
SKB3400110       2.8 1.1 1.5
SKB3400150       3.8 1.5 2
SKC3400220       5.1 2.2 3
SKC3400300       7.2 3 3
SKC3400400       9 4 5
SK2401 15.3 7.5 10 13 5.5 10
SK2402 21 11 15 16.5 7.5 10
SK2403 29 15 20 25 11 20
SK2404       29 15 20
SK3401 35 18.5 25 32 15 25
SK3402 43 22 30 40 18.5 30
SK3403 56 30 40 46 22 30
SK4401 68 37 50 60 30 50
SK4402 83 45 60 74 37 60
SK4403 104 55 75 96 45 75
SK5401 138 75 100 124 55 100
SK5402 168 90 125 156 75 125
SK6401 205 110 150 180 90 150
SK6402 236 200 200 210 110 150

690 VAC; ±10% 3 phase
  Normal Duty Heavy Duty
  Max Typical Motor Max Typical Motor
  Continuous Output Power Continuous Output Power
Order Code Current (A) (kW) (hp) Current (kW) (hp)
SK4601 22 18.5 25 19 15 20
SK4602 27 22 30 22 18.5 25
SK4603 36 30 40 27 22 30
SK4604 43 37 50 36 30 40
SK4605 52 45 60 43 37 50
SK4606 62 55 75 52 45 60
SK5601 84 75 100 63 55 75
SK5602 99 90 125 85 75 100
SK6601 125 110 150 100 90 125
SK6602 144 132 175 125 110 150





Automation Stock / Rome Electric
36 Westside Industrial Blvd.
Rome, GA 30165
Phone:706-413-1560
Fax: 706-232-2071
Email: sales@automationstock.com